🔌
Powered by AWG resistance table

Wire Gauge Calculator

Minimum wire size for given current, distance, voltage, and acceptable drop.

Recommended minimum
AWG 4 (21.2 mm²)
Required: ≤ 1.20 mΩ/m
Lower-voltage systems (12 V) require thicker wires for the same power. 24 V/48 V systems substantially reduce wire cost on long runs.

About

Voltage drop = 2 × distance × current × resistance per metre. The calculator returns the smallest standard AWG that keeps drop under your chosen percentage of system voltage.

How it works

  1. Enter the maximum continuous current (use breaker rating, not average).
  2. Use one-way distance (the calculator doubles it for the return path).
  3. Most off-grid systems target ≤ 3% drop; battery-to-inverter runs target ≤ 1%.

Frequently asked questions

Why does 12 V need such thick wires?+

Power = volts × amps. To deliver 1,200 W at 12 V you need 100 A; at 48 V only 25 A. Cable cross-section scales with current, so doubling system voltage roughly halves the copper needed for the same power and acceptable drop.

What voltage drop is acceptable?+

≤ 3% on PV-to-controller and battery-to-load runs is the off-grid standard. ≤ 1% on battery-to-inverter is recommended because inverters draw very high amps and even small drops cause heat and tripping under surge.

AWG or mm²?+

Same property, different units. AWG is North American, mm² is metric. Conversion is non-linear: AWG 12 ≈ 3.3 mm², AWG 8 ≈ 8.4 mm², AWG 4 ≈ 21.2 mm². The calculator shows both.

Can I use aluminium instead of copper?+

Yes for high-current battery interconnects (forklift cable). Aluminium has ~60% the conductivity of copper, so size up by ~2 AWG to match. Use anti-oxidation paste at terminations and never mix Cu/Al at a screw lug without a transition plate.